Features
Industrial grade design for tough industrial environment
Noise and interference protection. Efficiently block the interference of power and microwave
Standard equipment: independent RS232 Current Loop and Data Clock Output interface
5 stages of linear calibration, providing higher system accuracy
24 bits for internal A/D
Highly stabilized A/D sampling data
Equipped with self-diagnosis function, convenient for on-site maintenance
Specifications
| Model | JIF-15B |
| Built-in interface | RS232&Current Loop and Data Clock Output |
| Display | 7 weight digits weight;7 segments 0.8″high red LED |
| Dimension | 148(L)*200(W)*108(H) |
| Operation Temp. | -10℃- +40℃ ( +40℉-104℉) |
| Status indicators | 3Φ LED, Stable, Zero, Net, Gross, Tart |
| Min. Readability | ×1,×2, ×5,×10,×20,×50 |
| Loadcell ecxitation | DC 5V±5%, 120mA (up to 8*350Ω Loadcells) |
| Memory | Calibration parameters and function settings are saved into EEPROM |
| Input sensitivity | 0.15 μV / d and up to 1/60000 d |
| Max. Measured Voltage | -1mV – 39mv |
| AD Conversation/ Rate | △-∑; 80 times/sec. |